RONDON, Ivan; CALANCHE, Víctor y ROJAS, Francisco. Methodology for estimating the lifetime of 700 mva, at-4 autotransformer of guayana B substation due to overloads. uct [online]. 2013, vol.17, n.67, pp.57-67. ISSN 1316-4821.
Guayana "B" Substation has 7-400/115/20 kV reducers autotransformers of 700 MVA each one, of which the AT-4 transformer is the one with further deterioration due to constant overloads. Therefore, a method is required to estimate the deterioration and life time which diminishes. Research is evaluative type, because based on the simulation software in their model PTLOAD Top Oil and oil testing measurements and electrical insulation perfomed to the transformer was possible determine the decay time. There is agreement between the simulation results and testing measurements, which showed that the insulating state is still in good conditions and the estimated impairment based on the simulations is 85% which is 29,8 years compared to 34 been in use and keep that trend the transformer reach the end of their useful life in 2016. This study will provide a methodology that will shape the future burden that can endure the AT-4 for not accelerate aging.
Palabras clave : Aging; Lifetime; Deterioration; Cumulative Loss of Life; PTLOAD; Top Oil; Overload.